Features:SYSTEM OVERVIEW Line interactive tower UPS protects PCs and network workstations from blackouts, brownouts, surges and line noise. Maintains AC output during blackouts and continuously corrects brownouts as low as 83 volts back to usable 120V levels. Includes battery-supported and surge-only outlets, TEL/DSL line surge suppression, USB monitoring port, complete cabling and front panel LED indicators. PowerAlert monitoring software available via free download.
Voltage compatibility: 120V AC
Frequency compatibility: 60Hz OUTPUT
Output volt amp capacity (VA): 550
Output watt capacity (watts): 300
Output nominal voltage: 120V AC
Output voltage regulation: BATTERY MODE: PWM sine wave 120V +/-5%
Output frequency regulation: LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type: 6 NEMA 5-15R INPUT
Maximum input amps: 10A / 1200 watts Input connection type: NEMA 5-15P, right-angle plug Input cord length: 6 ft., 16 gauge
Recommended electrical service: 15A 120V BATTERY
Full load runtime: 4 minutes (550VA)
Half load runtime: 15 minutes (275VA) DC system voltage: 12 V DC
Typical battery lifespan: 3-6 years, depending on usage
Battery recharge rate: 3.6 hours to 90%
Replacement Battery Cartridge: RBC51 VOLTAGE REGULATION
Voltage regulation description: Line interactive voltage regulation corrects brownouts as low as 89V
Brownout correction: Input voltages between 89 and 104 are boosted by 14% LEDS ALARMS & SWITCHES
Front panel LEDs: 4 LEDs indicate performance conditions: GREEN online / GREEN voltage regulation enabled / RED on battery / YELLOW battery low/replace
Alarms: Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches: Includes 2 front panel switches - one main on/off power switch and one dual function alarm cancel / self test button SURGE / NOISE SUPPRESSION
AC surge suppression: 480 joules
AC suppression response time: Instantaneous
Dataline suppression: Tel/DSL
EMI / RFI AC noise suppression: Yes PHYSICAL
Shipping weight (lbs): 16
Shipping weight (kg): 7.3
Unit weight (lbs): 14.4
Unit weight (kg): 6.5
Unit Dimensions (HWD/in): 8.5 x 5 x 6.5
Unit Dimensions (HWD/cm): 21.6 x 12.7 x 16.5
Material of construction: PVC
Form factors supported: Tower
Cooling method: Convection
Battery Access: Battery access door allows user replacement of UPS batteries ENVIRONMENTAL
Operating Temperature: +32 to +104 degrees Fahrenheit0 to +40 degrees Celsius
Storage Temperature: +5 to +122 degrees Fahrenheit-15 to +50 degrees Celsius
Relative Humidity: 0 to 95%, non-condensing COMMUNICATIONS
Network monitoring port: USB Software and cabling included: USB cabling included, PowerAlert software available for free download at www.tripplite.com
WatchDog compatibility: Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications LINE / BATTERY TRANSFER
Transfer time from line power to battery mode: 2-4 milliseconds
Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 89 volts or less
High voltage transfer to battery power: Switches to battery power as line voltage increases to 139 volts or higher CERTIFICATIONS
Certifications: UL1778 (USA), cUL (Canada), Class B (emissions), NOM (Mexico), FCC Part 68 / Industry Canada
|